Would you like to inspect the original subtitles? These are the user uploaded subtitles that are being translated:
1
00:00:16,016 --> 00:00:20,519
since this is the number that ends up on the electricity bill for your data center,
2
00:00:20,820 --> 00:00:25,591
similar as how you receive electricity bill for your home each month
3
00:00:25,859 --> 00:00:31,730
Wei, the difference likely is that the one for your home is, hopefully, much lower
4
00:00:38,571 --> 00:00:44,176
it is the theoretical value of voltage
times the current expressed in ampere
5
00:00:45,879 --> 00:00:47,246
That is why the value of apparent power is indicated as VA or kVA
6
00:00:51,618 --> 00:00:57,222
The relationship between VA and Watt is indicated by the Power Factor or PF
7
00:01:16,609 --> 00:01:20,312
Every electrical device has a Power Factor on the input.
8
00:01:55,682 --> 00:02:00,986
For the output of the UPS this is important, and an example can be seen on this slide
9
00:02:10,563 --> 00:02:12,931
This is based on the formula on the slide,
10
00:02:15,068 --> 00:02:18,770
you multiply the Volt-Ampere
with the Power Factor.
11
00:02:28,381 --> 00:02:32,918
indicates the absolute maximum power that the equipment may consume,
12
00:02:33,419 --> 00:02:38,490
This assumes a fully loaded configuration with maximum CPU usage,
13
00:03:10,690 --> 00:03:13,158
to determine what the real expected
power consumption is going to be.
14
00:03:14,227 --> 00:03:15,460
to determine what the real expected
power consumption is going to be
15
00:03:16,029 --> 00:03:21,033
This can be very handy when
performing capacity planning calculations
16
00:03:21,334 --> 00:03:26,939
There are a few options for sizing the
computer room power requirements
17
00:03:27,407 --> 00:03:30,642
This slide is based on the metric system,
18
00:03:33,046 --> 00:03:35,414
where we can see the imperial system.
19
00:03:35,415 --> 00:03:39,418
| and look at somej letails for sizing power requirements
20
00:03:48,461 --> 00:03:54,066
This practice can still be followed as
a guidance for low density requirements,
21
00:04:00,406 --> 00:04:03,041
In case you calculate using square feet,
22
00:04:03,042 --> 00:04:06,245
you multiply the number with fifty Watt
23
00:04:06,813 --> 00:04:08,614
If your room is one hundred square meters,
24
00:04:32,005 --> 00:04:37,109
The best option is to look at the maximum
power which can be used in the rack
25
00:04:57,830 --> 00:05:02,367
In the data center, you don’t want to load
the breaker for more than 80 percent,
26
00:05:32,932 --> 00:05:38,537
and you need to realise that a data center Ihas an expected life span of 10-15 years
27
00:05:49,015 --> 00:05:50,282
on your cost to build
and your cost to operate
28
00:05:50,516 --> 00:05:51,249
on your cost to build and your cost to operate
29
00:05:51,784 --> 00:05:56,321
Note that in the industry it has become a trend to use the terminology
30
00:05:56,322 --> 00:05:59,524
"low", "medium" and "high density power,
31
00:05:59,525 --> 00:06:05,097
but there is no official definition
lin terms of what these numbers represent
32
00:06:14,407 --> 00:06:17,609
or do you have the luxury to
build your data center from scratch?
33
00:06:23,216 --> 00:06:24,015
you need to verify if there is
sufficient power available.
34
00:06:24,283 --> 00:06:29,888
If you build a new data center, you need to verify if the utility power company
35
00:06:29,889 --> 00:06:32,791
is able to supply the power that you need
36
00:06:33,292 --> 00:06:38,363
You could do a quick calculation for the purpose of obtaining an indication,
37
00:07:00,953 --> 00:07:07,058
is to perform a more detailed calculation,
to further fine tune your design
38
00:07:20,606 --> 00:07:26,178
As mentioned, from there onwards you need to consider future growth of the data centre,
39
00:07:30,983 --> 00:07:36,021
Once the numbers are known, you now know the load at the output of the UPS
40
00:07:40,860 --> 00:07:43,795
you add the efficiency factor of the UPS
41
00:07:44,363 --> 00:07:47,265
In addition, you need to add some buffer,
42
00:07:51,504 --> 00:07:54,139
If you want to be really on the safe side,
43
00:07:54,140 --> 00:07:59,978
you can add another 35%. but
in reality, 10-15% should be sufficient
44
00:08:27,373 --> 00:08:32,143
depending on whether you are using direct expansion (DX) or chilled water cooling
45
00:08:41,754 --> 00:08:47,092
Finely, you add up the total UPS input power, plus the raw power supply
46
00:08:47,093 --> 00:08:52,931
required for cooling and light, overf which a safety margin of 25% is added
47
00:08:53,466 --> 00:08:55,834
Note that these numbers are indicators,
48
00:09:07,280 --> 00:09:10,482
and look at your own specific situation
49
00:09:39,912 --> 00:09:40,912
So, once the main power is sized, you need
to start looking at your backucp power
50
00:09:40,913 --> 00:09:45,250
So, once the main power is sized, you need to start looking at your backup power,
51
00:09:48,421 --> 00:09:51,623
Generators need to be sized appropriately,
52
00:09:51,624 --> 00:09:57,729
undersized generators will not be able to support the load, causing unavailability
53
00:10:02,001 --> 00:10:07,272
since it will result in cylinder glazing which will create reliability issues
54
00:10:09,175 --> 00:10:14,746
you need to know the power requirements of the load in both kW and kVA.
55
00:10:14,747 --> 00:10:19,784
In addition, you need to review
potential inrush power requirements
56
00:10:24,090 --> 00:10:28,560
For example, when a heavy load such as a chiller plant kicks in
57
00:10:34,433 --> 00:10:39,204
and when that happens, the generator
must be able to support this.
58
00:10:39,205 --> 00:10:42,140
As mentioned previously, UPS and other systems generate harmonics,
59
00:10:52,752 --> 00:10:55,687
Thereforejreyiew theharmonics created,
60
00:11:25,751 --> 00:11:30,522
as a result of, for example, variable
speed drives in cooling systems.
61
00:11:31,057 --> 00:11:35,060
If you have equipment that generates a modest level of harmonics
62
00:11:41,701 --> 00:11:47,806
as it is the last resort of saving the data center against utility power outages
63
00:11:51,811 --> 00:11:54,446
but the principle of these batteries is
64
00:11:57,616 --> 00:12:00,885
in case of a power utility failure occurs
65
00:12:04,857 --> 00:12:07,492
do not exceed fifteen to twenty minutes,
66
00:12:07,493 --> 00:12:11,996
and do realise that once the utility power
is no longer present,
67
00:12:11,997 --> 00:12:14,666
air conditioners do no longer run either,
68
00:12:14,667 --> 00:12:20,205
unless additional dedicated UPS systems for air conditioners have been installed,
69
00:12:22,341 --> 00:12:28,213
So, in order to rely on your generator, you need to perform regular testing
70
00:12:28,748 --> 00:12:34,352
It is recommended to perform
a free running test at least once a month
71
00:12:46,332 --> 00:12:47,031
this for the purposes of the
generator its long term reliability
72
00:12:56,909 --> 00:13:01,412
It does not give you any information on the generator to start automatically
73
00:13:04,350 --> 00:13:09,954
nor does it tell if the generator is able to operate under full load conditions
74
00:13:31,510 --> 00:13:36,014
then the only option available would be to connect it to a load bank.
75
00:13:36,015 --> 00:13:39,184
which simulates a full load condition.
76
00:13:43,722 --> 00:13:46,357
which is not truly testing the generator
77
00:14:05,010 --> 00:14:10,315
and normally very little is used due to only testing being performed
78
00:14:16,188 --> 00:14:17,188
Some date center operators argue that as long as the generator runs,
79
00:14:39,578 --> 00:14:44,616
It is recommended to get a third party specialised company to take a fuel sample,
80
00:14:45,517 --> 00:14:46,150
and have it analysed in laboratory,
81
00:14:51,523 --> 00:14:56,628
In some of the colder countries you
may experience gelling of the diesel,
82
00:14:58,998 --> 00:15:04,269
This could hinder the proper flow and injection of fuel into the cylinders,
83
00:15:16,515 --> 00:15:19,751
Another often forgotten point by designers
84
00:16:19,912 --> 00:16:21,179
As the name suggests, it is a device that can assist in providing power
85
00:16:21,747 --> 00:16:23,648
As the name suggests, it is a device that can assist in providing power
86
00:16:27,653 --> 00:16:31,389
■ There are two main UPS| technologies deployed in the data center
87
00:16:35,127 --> 00:16:42,033
and the other one is known as the dynamic UPS system, also known as the rotary UPS
88
00:16:42,568 --> 00:16:48,139
The static UPS is called static, since it does not contain any moving parts
89
00:16:48,474 --> 00:16:54,545
The UPS consists of electronic components,
such as the rectifier and the inverter
90
00:17:17,169 --> 00:17:22,440
although alternative energy stroage
solutions are available in the the market
91
00:17:23,008 --> 00:17:24,175
Adynamic or rotary UPS is a system
which is built up out of moving parts
92
00:17:24,209 --> 00:17:28,212
A dynamic or rotary UPS is a system which is built up out off moving parts.
93
00:17:40,526 --> 00:17:43,694
Static UPS systems are relatively complex,
94
00:17:51,703 --> 00:17:54,338
which is at the heart of the UPS system.
95
00:18:19,364 --> 00:18:24,936
Batteries are a cost factor, as they need to be replaced after a number of years.
96
00:19:07,846 --> 00:19:08,646
Dynamic UPS systems are only available in the higher power ratings
97
00:19:27,166 --> 00:19:31,936
Dynamic UPS systems are very, heavy compared to static UPS systems
98
00:19:45,551 --> 00:19:50,821
Dynamic UPS systems are very noisy and often require a room with sound proofing
99
00:19:55,093 --> 00:20:00,131
and there is no need for batteries apart from a few batteries to start the engine
100
00:21:01,526 --> 00:21:03,928
This makes it very confusing for the data center choose the correct UPS for its purpose
101
00:21:05,330 --> 00:21:06,030
This makes it very confusing for the data center to choose the correct UPS for its purpose.
102
00:23:31,543 --> 00:23:34,612
Should the input fail or exceed the defined allowable input window for frequency and voltage,
103
00:23:35,013 --> 00:23:38,215
Should the input fail or exceed the defined allowable input window for frequency and voltage,
104
00:24:06,178 --> 00:24:06,744
and in some data centers, these UPS systems
are placed inside the ICT equipment racks.
105
00:28:38,316 --> 00:28:39,483
Once the UPS switches to static bypass, it needs immediate attention to correct the situation.
106
00:28:39,884 --> 00:28:40,284
Once the UPS switches to static bypass, it needs immediate attention to correct the situation.
107
00:28:41,986 --> 00:28:44,655
Once the UPS switches to static bypass, it needs Immediate attention to correct the situation.
108
00:32:33,584 --> 00:32:34,851
the UPS could for example run in VI mode
109
00:34:00,038 --> 00:34:02,973
compared to the conventional UPS systems,
110
00:49:06,643 --> 00:49:07,310
since the technology is very reliable,
111
01:30:58,486 --> 01:30:59,252
tor with the [ ^ lower] resistance will carry the [ ^ mos
112
01:31:03,424 --> 01:31:16,236
Transformer is required. Which K-factor do you look f(
113
01:31:31,152 --> 01:31:32,719
ntenance bypass mode. Which UPS technology are you
114
01:31:32,954 --> 01:31:38,391
*m to prevent unsafe temperatures during charging/dis
115
01:32:21,135 --> 01:32:23,537
Copyright EPl#. All rights reserved, no reproduction in part or in full
116
01:32:37,018 --> 01:32:39,386
Copyright (Pis. All rights reserved, no reproduction in part or in full
117
01:33:12,286 --> 01:33:16,022
which is at extreme high frequency levels
118
01:33:20,795 --> 01:33:26,099
Focusing on electromagnetic fields, you need to look at the low frequencies,
119
01:33:26,801 --> 01:33:27,767
Being multiples of fifty or sixty hertz,
120
01:33:31,906 --> 01:33:33,807
depending on the country in which you are operating your data center
121
01:33:37,311 --> 01:33:37,811
When you visualize this
on the electromagnetic spectrum,
122
01:33:50,324 --> 01:33:56,463
One part is called the electrical fields,
which is indicated by the letter E.
123
01:34:14,515 --> 01:34:17,717
Coming back to the electrical fields,
124
01:34:21,455 --> 01:34:26,693
Therefore, the higher the voltage.
also the higher the E fields present
125
01:34:27,962 --> 01:34:28,628
Therefore, the higher the voltage,
also the higher the E fields present
126
01:34:32,600 --> 01:34:38,772
so the more current that's consumed, the higher the magnetic fields,
127
01:34:42,209 --> 01:34:48,048
Specifically in the United States of
America, this could be a bigger concern.
128
01:34:48,049 --> 01:34:51,985
since it is using a low voltage system.
129
01:35:01,595 --> 01:35:02,262
Other parts of the world operate on 380 or 415 volt phase to phase.
130
01:35:19,146 --> 01:35:23,650
there is not much to be worried about when it comes to electric fields,
131
01:35:32,993 --> 01:35:38,031
On the secondary side, the voltage is relatively low and that will not change,
132
01:35:38,032 --> 01:35:40,667
since the voltage is always stable
133
01:35:51,045 --> 01:35:57,450
Magnetic fields, however, are created by current, which could vary day by day,
134
01:35:57,451 --> 01:36:00,353
depending on the load in your data center
135
01:36:00,354 --> 01:36:06,493
This automatical results in having more concerns about magnetic fields,
136
01:36:09,396 --> 01:36:12,866
The strength of magnetic fields is often
137
01:36:25,913 --> 01:36:27,947
So, a quick recap: electric fields are known as E fields and involve voltage,
138
01:36:27,948 --> 01:36:32,819
So, a quick recap: electric field are
known as E fields and involve voltage.
139
01:36:57,278 --> 01:36:58,578
you probably want to know
where these fields are coming from
140
01:37:10,591 --> 01:37:11,124
and in the data center this comes from the High Tension transformers,
141
01:37:11,125 --> 01:37:14,460
the UPS systems, power generator
sets, main power cables, etc.
142
01:37:22,536 --> 01:37:27,340
the concern is more about
the main power that goes into an EDU
143
01:37:30,211 --> 01:37:34,514
you could look at anything which carries a current of more than 100 amperes
144
01:37:34,782 --> 01:37:39,586
Another possible concern is the lightning strike protection system
145
01:37:43,057 --> 01:37:48,061
to the ground drop in the soil may appear on the outside wall of the computer room
146
01:37:48,462 --> 01:37:49,095
When lightning strikes the building,
147
01:38:01,909 --> 01:38:08,815
So, especially when an existing building is selected to become your date center,
148
01:38:16,757 --> 01:38:22,896
or EMI and RFI could potentially cause
equipment malfunctioning
149
01:38:22,897 --> 01:38:27,133
Here are a few examples
of some of the manufacturer's manuals,
150
01:38:27,134 --> 01:38:28,368
in which they inform customers with some of the possible effects of EMF
151
01:38:55,329 --> 01:38:59,098
is occurring in the radio frequency band
152
01:39:16,884 --> 01:39:22,755
This slide demonstrates some of the effects of EMF on a microprocessor chip
153
01:39:37,638 --> 01:39:42,141
and it's something that you would normally
not see in a data center environment
154
01:39:42,409 --> 01:39:47,714
Another problem, which does frequently
occur, is the Hot Electron effect.
155
01:39:57,825 --> 01:40:04,197
the electrons flow from the source to the drain over the N and P layers of the chip,
156
01:40:09,003 --> 01:40:14,574
Due to the effects of EMF on a chip,
it is possible that the electron's flow
157
01:40:26,787 --> 01:40:32,091
if power cables and cooper-based network
cables are too close to each other
158
01:40:37,965 --> 01:40:43,803
which could lead to poor network performance or even collapse of a network
159
01:40:43,804 --> 01:40:50,176
This will occur in both unshielded and Shielded twisted pair network cabling
160
01:40:54,681 --> 01:40:59,986
was created to combat alien cross-talk between network cables.
161
01:41:00,220 --> 01:41:06,659
And it certainly wasn’t developed to avoid the effects of EMF on network cabling
162
01:41:21,241 --> 01:41:23,643
The human body has some magnetite,
163
01:41:27,915 --> 01:41:31,384
EMF has a potential impact on magnetite,
164
01:41:42,563 --> 01:41:47,633
This is exactly the reason why some frequent international travelers
165
01:41:54,842 --> 01:41:56,909
which then helps them to avoid the
issues that are associated with jet lag
166
01:42:30,944 --> 01:42:31,477
that there are a lot of standards and guidelines addressing EMF and RFI,
167
01:42:32,446 --> 01:42:34,614
that there are a lot of standards and guidelines addressing EMF and RFI,
168
01:42:34,982 --> 01:42:35,448
that there are a lot of standards' and guidelines addressing EMF and RFI,
169
01:42:50,063 --> 01:42:55,401
The standard indicates the acceptable
levels for EMF surrounding equipment
170
01:43:02,176 --> 01:43:02,842
Exceeding the level of 37.5 milligauss
171
01:43:03,110 --> 01:43:07,613
may result in the system being, affected by levels no longer acceptable,
172
01:43:10,017 --> 01:43:15,354
The NCRP, the National Council
on Radiation Protection and Measurements
173
01:43:19,593 --> 01:43:25,431
to which humans should be exposed to
for a longer period of time.
174
01:43:32,906 --> 01:43:36,876
Some countries may apply stricter limits,
175
01:43:46,420 --> 01:43:53,359
An electromagnetic pulse or EMP is
a short burst of electromagnetic energy
176
01:43:53,360 --> 01:43:55,995
This pulse has the capability to bum out
177
01:44:05,572 --> 01:44:07,974
generating a high electromagnetic pulse,
178
01:44:12,346 --> 01:44:16,749
It is not unthinkable that if your country does end up in a state of war
179
01:44:20,187 --> 01:44:22,588
to knock out all communication networks,
180
01:44:26,059 --> 01:44:31,364
Another device capable of generating
an extreme high electromagnetic pulse
181
01:44:31,632 --> 01:44:35,034
is by means of a compression generator
182
01:51:16,403 --> 01:51:30,816
.IF exoosure levels towards humans?
19463
Can't find what you're looking for?
Get subtitles in any language from opensubtitles.com, and translate them here.