Would you like to inspect the original subtitles? These are the user uploaded subtitles that are being translated:
1
00:00:28,228 --> 00:00:32,998
| And on this slide we can see what that means in terms of the cost for downtime,
2
00:00:33,867 --> 00:00:34,266
| And on this slide we can see what that [means in terms of the cost for downtime,
3
00:01:09,135 --> 00:01:12,304
Therefore, to have at least an indication,
4
00:01:31,458 --> 00:01:37,329
| there are other factors to consider if [you wish to have a more accurate number
5
00:01:40,533 --> 00:01:45,871
whereby your company has a higher revenue E thesummer^mparedtottie winter,
6
00:02:07,160 --> 00:02:08,260
knowing that the actua£cos£of downtime per hour is in fact significantty higher!
7
00:02:08,294 --> 00:02:10,362
knowing that the actua£cost of downtime
8
00:02:10,463 --> 00:02:13,232
knowing that the actual cost of downtime [per hour is in fact significantly higher.
__________________________w____________
9
00:02:13,766 --> 00:02:19,571
■ With this information known you can J tart using the number to create awareness
10
00:02:50,937 --> 00:02:55,974
and there are many infrastructure elements
■required to build up a data centre )
11
00:02:56,242 --> 00:02:58,243
I Together all these elements will need to create a reliable data center environment,
12
00:04:00,340 --> 00:04:01,340
are you able to identify all components
13
00:04:29,335 --> 00:04:32,771
and determine what can or needs to be done
14
00:05:20,119 --> 00:05:23,288
Other factors may come from human origin.
15
00:05:23,289 --> 00:05:26,792
this relates to people executing processes
16
00:05:57,623 --> 00:05:58,924
Attacking the network doesn't require any physical presence at the data center site
17
00:05:59,559 --> 00:06:00,125
Attacking the network doesn't require any ^physicalI presence at the data center site
18
00:06:00,693 --> 00:06:01,860
Attacking the network doesn't require any physical presence at the data center site
19
00:06:02,261 --> 00:06:03,362
Attacking the network doesn't require any physical presence at the data center site
20
00:06:03,730 --> 00:06:08,533
The network cable is bypassing any physical
security measures of a data center.
21
00:06:15,141 --> 00:06:15,607
and they can do so at any moment in time
22
00:06:17,310 --> 00:06:18,110
23
00:06:18,378 --> 00:06:22,914
| It is, therefore, no surprise that the number of network attacks is increasn
1
24
00:07:24,010 --> 00:07:29,848
It should be noted that sometimes hardware failures are the result of a human error
25
00:07:34,921 --> 00:07:38,990
B tt is, therefore, very important for the data center to have competent personnel,
26
00:07:38,991 --> 00:07:40,192
It is, therefore, very important for the ata center to have comoetent oersonnel
27
00:07:45,565 --> 00:07:48,433
which they are managing and operating
28
00:07:48,701 --> 00:07:56,408
| So, the human error is one of the large contributors to the data center downtime
29
00:08:03,816 --> 00:08:05,784
or due to poor execution of processes
30
00:08:06,252 --> 00:08:06,718
or due to poor execution off processes.
31
00:08:22,201 --> 00:08:28,640
I This is very uniortunaiB, since often when alarms are attended to promptly
32
00:09:03,409 --> 00:09:08,713
This means that if there is noisep the ground cable going into the UPS,
33
00:09:32,638 --> 00:09:38,743
Another potential cause of unavailability nay be caused by electromagnetic fields,
34
00:09:39,378 --> 00:09:40,211
or shortly known as EMF
35
00:09:57,096 --> 00:09:58,630
| High levels of EMF can cause issues on computing and network equipment,
36
00:09:59,265 --> 00:10:01,399
High levels of EMF can cause issues on computing and network equipment,
37
00:10:21,020 --> 00:10:22,854
| but also temperature and humidity, [values which are fluctuating too much
38
00:10:26,359 --> 00:10:26,891
but also temperature and humidity, alues which are fluctuating too much
39
00:10:30,062 --> 00:10:35,934
■ Another environmental factor isj Pollution or contamination coming from,
40
00:10:38,571 --> 00:10:41,806
Dust and gases, such as hydrogen sulfide,
41
00:11:08,134 --> 00:11:13,972
S| Unfortunately, most data centers! e not ready for tomorrow's technology,
42
00:11:20,079 --> 00:11:23,314
which is the average lifespan of a data center
43
00:11:23,549 --> 00:11:29,954
Even ICT equipment manufacturers H not be able to provide you the power,
44
00:11:33,392 --> 00:11:36,594
which they may manufacture in the future
45
00:11:52,011 --> 00:11:54,646
Hence, when you design a data center.
46
00:12:12,665 --> 00:12:14,632
If any of these limitations are reached,
the data center is maxed out
47
00:12:15,167 --> 00:12:15,567
1 It is, therefore, very well possible [that the computer room is half emj
48
00:12:54,807 --> 00:12:59,844
Problems in the data center environment could lead to serious business losses
49
00:13:09,922 --> 00:13:13,124
The data center is complex and dynamic,
50
00:13:13,125 --> 00:13:19,297
and capacity needs to be well managed for physical space, power and cooling
51
00:13:19,498 --> 00:13:25,370
You have_alsojearned that most of the downtime is caused by the human error,
52
00:15:17,850 --> 00:15:18,249
The bad newsjsjhat there is no official alobal standard for data centers
53
00:15:18,317 --> 00:15:19,851
| The bad news is that there is no
official Global standard for data centers
54
00:15:19,852 --> 00:15:22,587
The bad news is that there is no official global standard for data centers
55
00:15:22,888 --> 00:15:25,523
Since there is no worldwide standard,
56
00:15:25,624 --> 00:15:30,061
it is hard for data centers and customers
■to have a dear reference point
57
00:15:36,702 --> 00:15:42,073
that datacenter_operators make all sorts of claims, to impress their customers
58
00:15:42,074 --> 00:15:47,645
For example, it is claimed that the data (center is a grade A dass a data center,
59
00:15:47,646 --> 00:15:52,984
| some even make statements such as [having a world class data center facility,
60
00:15:55,087 --> 00:15:58,289
All this is mostly a marketing message.
61
00:16:08,667 --> 00:16:14,238
| It is, therefore, important to ask |those data center operators or owners,
62
00:16:14,239 --> 00:16:18,476
what reference point they are ising Bo make such daims I
63
00:16:23,315 --> 00:16:28,419
There are several best practices!
and national standards, which can be used
64
00:16:38,998 --> 00:16:44,102
can be applied to any type of data center, Min any location in the world. B
65
00:16:44,370 --> 00:16:48,339
TIA 942 is using a classification system,
66
00:17:12,331 --> 00:17:18,436
A fact, that which not everyone realizes
is that the UptimeTier definition
67
00:17:18,437 --> 00:17:22,940
only addresses the power and cooling infrastructure of the data centre.
68
00:17:27,212 --> 00:17:31,749
are not covered in the Tier topology ■definitions of the Uotime Institute
69
00:17:41,026 --> 00:17:41,659
I Hence, what they have produced |is a white paper or guideline at best,
70
00:17:42,027 --> 00:17:42,927
| Hence, what they have produced |is a white paper or guideline at best,
71
00:17:43,595 --> 00:17:46,097
| Hence, what they have produced! te a white paper or guideline at best.
72
00:17:49,802 --> 00:17:54,572
TIA stands for Telecommunications infrastructure Association" I
73
00:17:59,378 --> 00:18:05,750
TIA have taken the high level, Tier level [definitions from the Uptime Institute,
74
00:18:09,188 --> 00:18:09,954
such as architectural, telecommunications,
fire safety and other criteria
75
00:18:10,055 --> 00:18:15,026
such as architectural, telecommunications,
fire safety and other criteria.
76
00:18:22,734 --> 00:18:27,805
to add more distinction to the standards.
land to avoid confusion in the market
77
00:18:28,040 --> 00:18:33,644
| However, very often data centers which are designed as per TIA-942
78
00:18:43,755 --> 00:18:46,157
and it is therefore, fully transparent,
79
00:18:46,158 --> 00:18:50,928
Bas to what the data center has| emented from a design perspective,
80
00:19:22,594 --> 00:19:28,166
J and using it as a design guide serves la better purpose than an auditable standard
81
00:19:28,167 --> 00:19:33,471
The EN 50600 is a European standard
82
00:19:33,472 --> 00:19:38,776
so far the adoption is slowly going up, Band that may change in the future,
83
00:20:06,505 --> 00:20:12,043
which are created by product manufacturers ■commonly referred to as white papers,
84
00:20:17,516 --> 00:20:18,649
B Although these documents^ contain interesting information,
85
00:20:18,650 --> 00:20:24,255
| you should also realize that there may be commercial reasons behind these documents
86
00:20:24,523 --> 00:20:30,661
In other words, the vendor may want ho influence the end user's thinking,
87
00:20:30,662 --> 00:20:35,466
B which then, hopefully leads tog end-user purchasing their solutions
88
00:20:35,734 --> 00:20:40,771
| There are several organizations) working on new standards and guidelines,
89
00:20:40,772 --> 00:20:43,441
trying to capture a piece of the market
90
00:20:47,679 --> 00:20:51,182
since most of the so-called new standards
91
00:20:51,183 --> 00:20:55,686
have similar principles
compared to the existing standards,
92
00:21:24,216 --> 00:21:28,319
an overview of the most common ■data center standards applied.
93
00:21:28,587 --> 00:21:34,158
| As mentioned, the specification from [Uptime is not a standard, but a guideline
94
00:21:34,426 --> 00:21:38,429
The Uptime Institute is a commercial [consulting organization, |
95
00:21:38,430 --> 00:21:44,035
| and not a standards development organization, such as the TIA and ISO,
96
00:21:44,036 --> 00:21:49,874
which standards, since you may apply muttiple standards depending on your need,
97
00:21:49,875 --> 00:21:54,879
or guideline to apply is a choice
of the data center's owner or operator,
98
00:21:58,884 --> 00:22:02,620
More and more data center owners Band operators apply standards,
99
00:22:06,058 --> 00:22:08,459
the overall risk o£a data center setup,
100
00:22:27,579 --> 00:22:32,650
| All off the standards and guidelines define various classes off conformity,
101
00:22:40,592 --> 00:22:43,527
Do realize that in terms of availability,
102
00:22:43,528 --> 00:22:49,900
the numbers are expected availability, and therefore, cannot be guaranteed
103
00:23:01,580 --> 00:23:06,617
That also means that the document
they produce is not an official standard,
104
00:23:35,347 --> 00:23:40,651
wh«~eas for Uptime you are fully dependent Hon them for now and in the future
105
00:24:04,042 --> 00:24:04,575
or is it based on findings, supported by an independent auditor's report,
106
00:24:04,676 --> 00:24:05,576
or is it based on findings, supported bv an indeoendent auditor's reoort
107
00:24:05,777 --> 00:24:07,178
or is it based on findings, supported
indent auditor's n
108
00:24:07,546 --> 00:24:09,613
or is it based on findings, supported by an independent auditor’s report,
109
00:24:09,881 --> 00:24:15,719
followed with certification that is issued by an accredited certification body
110
00:24:30,402 --> 00:24:36,707
J Without going into too much detail, this slide demonstrates a helicopter view
111
00:24:40,712 --> 00:24:43,647
In case you are interested in the details,
112
00:24:46,551 --> 00:24:53,190
or attending in the future the CTDC course after you have passed the CDCP exam,
113
00:24:53,191 --> 00:24:59,029
the CT DC course is the design consultant
course for the TIA-942 standard
114
00:25:03,301 --> 00:25:09,707
I which has a single path for distribution |of power and cooing without redundancy
115
00:25:10,008 --> 00:25:15,846
The power and cooling infrastructure have ■sufficient capacity to serve the IT load
116
00:25:22,954 --> 00:25:25,389
This is a relative low cost data center,
117
00:25:34,966 --> 00:25:40,271
fa Rated-2 data center also hasy single path for power and cooling,
118
00:25:55,186 --> 00:26:01,258
| Rated-3 data centre is often indicated as concurrently maintainable data center,
119
00:26:01,259 --> 00:26:06,330
| this means that the data center can
undergo any form of planned maintenance
120
00:26:08,533 --> 00:26:09,033
without causingIT downtime
121
00:26:11,503 --> 00:26:11,969
This setup requires a minimuni
of two paths for power and cooling
122
00:26:18,543 --> 00:26:21,512
and the other path to be on standby,
123
00:26:27,852 --> 00:26:34,491
data centers activate both feeds, since Ball the equipment is installed anyway
124
00:26:34,759 --> 00:26:41,432
This has benefits, but from a Rated 3
■design criteria it is not required, f
125
00:26:47,272 --> 00:26:53,377
A Rated-4 datacenter is often described as a fault tolerant data center
126
00:27:18,403 --> 00:27:21,305
and disaster recovery plans in place
127
00:27:21,573 --> 00:27:28,212
Rated-4 data center has a minimal requirement ■of two paths for power and cooling,
128
00:27:33,885 --> 00:27:34,318
which both are active so that it can jtaciiitate an automatic switchover,
129
00:27:34,319 --> 00:27:38,288
in case one supply path develops a fault
130
00:28:06,484 --> 00:28:11,522
and^skjyourselfwrthjhe information that you have from the course so far,
131
00:28:49,327 --> 00:28:52,896
| such as electrical installation, fire protection and other areas of interest
132
00:28:52,897 --> 00:28:54,932
| such as electrical installation, fire protection, and other areas of interest
133
00:28:55,900 --> 00:28:58,402
On this slide, therearea few examples,
134
00:28:58,403 --> 00:29:03,974
| but as you can imagine, many other of such standards exist in each country
135
00:29:03,975 --> 00:29:08,779
I Realize, however, that these standards are mostly general in nature,
136
00:29:08,780 --> 00:29:13,784
|and were not developed to specifically address the needs of a data center
137
00:29:14,052 --> 00:29:14,685
For example, the standard for rounding specifies in most cases
138
00:29:15,053 --> 00:29:16,787
| For example, the standard ,or rounding specifies in most cases
139
00:29:19,157 --> 00:29:24,728
that the ground resistance in the building Its allowed to be between 10-25 Ohms
140
00:29:25,230 --> 00:29:31,368
However for data center its ideal to have a ground resistance of less than 1 Ohm,
141
00:29:31,636 --> 00:29:34,538
or at least a maximum level of five Ohm
142
00:29:35,073 --> 00:29:37,474
Itis. therefore, strongly recommended
143
00:29:38,710 --> 00:29:40,010
to make sure that contractors are notonlyinstrudedtofol^
144
00:29:46,551 --> 00:29:48,285
■ in addition to that you shoukf rovide more detailed requirements,
145
00:30:25,323 --> 00:30:28,492
to venfy what thelocal standards are,
146
00:30:28,493 --> 00:30:33,597
to make sure the data center fully compliant to those standards
147
00:30:41,039 --> 00:30:44,474
and possible liabilities from occurring
148
00:30:46,344 --> 00:30:51,415
it would be good to create an overview
of local regulations and standards
149
00:30:51,416 --> 00:30:58,288
| so that an inventory is readily available for all involved to source from
150
00:31:00,425 --> 00:31:06,830
you have learned that there is no
worldwide accredited data center standard
151
00:31:18,243 --> 00:31:23,847
On national level, there are
often a variety of standards available,
152
00:31:55,046 --> 00:31:59,583
components based on N+1 is a characteristic of which R
153
00:32:44,996 --> 00:32:46,897
[Site selection is the activity of choosing ■the location to set uo vour data center
154
00:32:46,898 --> 00:32:50,634
Site selection is the activity of choosing Ihe location to set up your data center
155
00:32:51,703 --> 00:32:54,171
| There are many chaMengesf when performing site selection
156
00:33:01,479 --> 00:33:03,914
but also include business requirements
157
00:33:11,322 --> 00:33:15,592
| Engineers are normally!
responsible for evaluating the site,
158
00:33:22,233 --> 00:33:28,605
I The business tends to review the site location
based on business criteria, such as
159
00:33:31,843 --> 00:33:36,847
What is the cost of the land or building
area per square foot or square meter"
160
00:33:37,115 --> 00:33:43,487
| What is the cost of utilities, such as water and electricity, and so on
161
00:33:47,992 --> 00:33:54,164
which could reduce the cost of operations and create a faster return on investment,
162
00:34:03,975 --> 00:34:08,245
the business owner will
ultimately make the final decision,
163
00:34:08,246 --> 00:34:13,550
which could result in technical
potentially having to be compromised
164
00:34:21,492 --> 00:34:27,898
manageability and potential compliance to compulsory and voluntary standards
165
00:34:28,399 --> 00:34:33,203
It is, therefore, of utmost importance
that the technical evaluation group
166
00:34:45,616 --> 00:34:46,450
so that business decision makers
can take those into consideration
167
00:34:50,221 --> 00:34:55,792
one of the absolute minimum requirements,
■then these needs to be documented
168
00:34:55,793 --> 00:34:58,728
Make sure that everyone understands,
169
00:35:00,965 --> 00:35:01,398
and ultimately accepts the decision
and its potential future impact
170
00:35:02,700 --> 00:35:04,868
and ultimately accepts the decision
■and its potential future impact
171
00:35:05,403 --> 00:35:10,674
| In this way, it can be avoided that later individuals are blamed for issues,
172
00:35:10,942 --> 00:35:12,843
which were beyond their control,
173
00:35:12,844 --> 00:35:18,115
since they were simply overruled
by the business decision makers
174
00:35:32,497 --> 00:35:37,267
I You also need to ensure that you can achieve this scalability required,
175
00:35:51,916 --> 00:35:53,550
In order to build, and eventually
operate at a data center,
176
00:35:53,551 --> 00:35:56,386
■ you need to carefully select and implement the equipment that you need
177
00:35:56,387 --> 00:35:58,288
| you need to carefully select and implement the equipment that you need
178
00:36:13,204 --> 00:36:17,474
maintenance, secunty. safety and so on
179
00:36:18,509 --> 00:36:23,847
| Another important aspect is to ensure that ■decisions made during the site selection
180
00:36:24,115 --> 00:36:30,487
do not impact compliance to standards, as rectification can often be very costly,
181
00:36:35,526 --> 00:36:39,763
This could lead to potential non
compliances to the standards chosen,
182
00:36:54,278 --> 00:36:56,947
Obviously, there is a limit in terms |of how much can be planned for,
183
00:37:11,896 --> 00:37:17,500
also realize that many data centers
suffer from tremendous oversizing,
184
00:37:21,239 --> 00:37:22,539
on the organization's contribution to environmental sustainability.
185
00:38:25,436 --> 00:38:30,507
Natural hazards are events that may happen
and there is little you can do about it
186
00:38:40,885 --> 00:38:45,922
For example, if you are building
a data center in an earthquake prone area,
187
00:38:50,461 --> 00:38:54,998
■ Does it mean that you can never build a data center in an area like that?
188
00:38:59,203 --> 00:39:05,875
but the cost to build will increase due to
the additional risk mitigation controls,
189
00:39:38,809 --> 00:39:42,545
Some examples are listed on this slide
190
00:39:47,918 --> 00:39:49,419
You could consider a plenty of others,
191
00:39:53,691 --> 00:39:58,228
chemical plants, oil refineries and so on
192
00:39:58,696 --> 00:40:01,931
Try to avoid all these potential hazards
193
00:40:06,170 --> 00:40:09,372
and the hazards that you
have identified
194
00:40:47,378 --> 00:40:53,483
Power distribution network can potentially ■cause electromagnetic field radiation,
195
00:40:53,484 --> 00:40:56,719
which can cause issues on your equipment
196
00:41:19,610 --> 00:41:22,312
Are you ready to perform a site selection?
197
00:41:55,813 --> 00:41:56,713
j So, perhaps, put this on your action list for the next couple of months or so
198
00:42:00,284 --> 00:42:06,422
! Perform a site selection assessment to dentify the potential hazards around you,
199
00:42:16,300 --> 00:42:16,833
ideally, you try to build the data center in a light industrial or urban area
200
00:42:17,401 --> 00:42:21,004
ideally, you try to build the data center
in a light industrial or urban area
201
00:42:21,672 --> 00:42:22,372
ideally, you try to build the data center in a light industrial or urban area
202
00:42:29,313 --> 00:42:34,884
In certain part of the world peaople often
demonstrate around police facilities
203
00:42:42,326 --> 00:42:45,495
With that said, you can probably recall
204
00:42:58,776 --> 00:43:05,448
I If there is a natural disaster or other
calamities causing many injured people
205
00:43:20,331 --> 00:43:23,266
because the entire area is sealed off
206
00:43:24,335 --> 00:43:27,503
The fire department is your best friend
207
00:43:40,250 --> 00:43:46,656
Try to stay away from potential high risk
targets, such as government buildings
208
00:43:46,657 --> 00:43:50,393
power, radio, TV stations and embassies.
209
00:44:16,153 --> 00:44:16,686
| causing a potential uproar for people to go on the street and to demonstrate
210
00:44:16,687 --> 00:44:17,487
| causing a potential uproar for people to go on the street and to demonstrate
211
00:44:21,191 --> 00:44:23,893
You can simply not be careful enough
212
00:44:39,843 --> 00:44:41,177
I As mentioned, these fields can [have an impact on IT equipment.
213
00:44:57,094 --> 00:45:02,465
[ may be tie first ones that wil be^ attacked in the event it ends up in a war
214
00:45:25,155 --> 00:45:29,392
| Now that we have looked at the site selection criteria for the location
215
00:45:35,999 --> 00:45:38,401
and then design and build the data center
216
00:45:38,402 --> 00:45:43,206
| taking into account all your requirements and the nice-to-have ones
217
00:45:59,389 --> 00:46:04,961
with the difference that in case of a build [scenario that has nothing existing yet,
218
00:46:05,596 --> 00:46:08,164
| and hence, you may have more control over the possible outcome
219
00:46:09,233 --> 00:46:15,872
However, poor design or mistakes may end up worse compared to existing buildings
220
00:46:16,140 --> 00:46:20,910
There is a reason why earief I explained ■the need for data center standards,
221
00:46:20,911 --> 00:46:27,817
since the standards can help you to prevent making possible design mistakes
222
00:46:50,941 --> 00:46:56,546
Do not ask the real estate agent, who is
trying to sell or rent the space to you,
223
00:47:06,089 --> 00:47:06,789
In other words, he or she will most
likely tell you not the entire truth
224
00:47:07,191 --> 00:47:12,762
Ask existing tenants if present, and while ■doing so, ask key critical questions,
225
00:47:33,517 --> 00:47:38,321
| Building codes are very important, as these are the rules and regulations
226
00:47:38,322 --> 00:47:42,792
to tell you what you can and
specifically cannot do in the building,
227
00:47:54,471 --> 00:47:59,542
This means you will now have to rely on the generator of the building owner
228
00:48:00,077 --> 00:48:05,915
| This will raise immediate questions as to whether there is enough capacity,
229
00:48:05,916 --> 00:48:11,287
and how they manage it, such that there Its no power capacity shortage over time
230
00:48:11,521 --> 00:48:14,190
Another question that comes to mind,
231
00:48:14,191 --> 00:48:19,729
how frequency do they test and perform maintenance on the generator"?
232
00:48:50,627 --> 00:48:52,428
These locations could lead to security Bissues, and also potential flooding
233
00:48:52,429 --> 00:48:56,766
These locations could lead to security ■issues, and also potential flooding
234
00:49:04,207 --> 00:49:10,546
Do realize that a location too high in the building is not a great location either,
235
00:49:36,073 --> 00:49:39,275
Another aspect is to plan for growth
236
00:49:47,284 --> 00:49:51,754
| and it is simply not possible to predict the business nor the technology
237
00:49:54,958 --> 00:49:58,661
| Therefore, growth should be properly defined in terms of its limits,
238
00:49:59,496 --> 00:50:00,029
| Therefore, growth should be property defined in terms of its limits,
239
00:50:04,267 --> 00:50:07,203
to be accommodated in a data center
240
00:50:08,672 --> 00:50:10,740
Consider all security requirements
241
00:50:13,310 --> 00:50:17,847
J it may be desirable to build a fence or a wall around the building,
242
00:50:24,755 --> 00:50:29,258
| and can you separate visitor car parks from those of your own staff?
243
00:50:37,768 --> 00:50:43,606
Try to avoid windows in the
computer room and its supporting areas
244
00:50:50,347 --> 00:50:50,946
and glass itself functions)
as a conductor of heat and cold air
245
00:51:06,263 --> 00:51:07,363
Don't forget that most existing
buildings are built for office purposes,
246
00:51:07,631 --> 00:51:10,266
Don’t forget that most existing
buildings are built for office purposes
247
00:51:10,734 --> 00:51:11,534
| Don*t forget that most existing! [buildings are built for office purposes
248
00:51:11,535 --> 00:51:14,003
and cannot always withstand the load
required by data center equipment
249
00:51:14,004 --> 00:51:17,373
and cannot always withstand the load ■required by data center equipment
250
00:51:23,246 --> 00:51:23,712
| what the floor loading capabilities
are, to avoid anyissues in the future
251
00:51:29,619 --> 00:51:35,991
Slab to slap height in the building
is important from a cooling point of view
252
00:51:49,573 --> 00:51:51,140
using dimensions sufficient^ to support the cooling infrastructure
253
00:52:06,523 --> 00:52:11,861
You also need to evaluate how much power capacity is available in the building,
254
00:52:11,862 --> 00:52:15,331
and if future expansions are possible
255
00:52:15,565 --> 00:52:19,301
if such need may be present in the future
256
00:52:21,438 --> 00:52:27,543
it is necessary to review if dual utility power cables are entering the bolding,
257
00:52:32,349 --> 00:52:37,119
Furthermore, investigate where the power cables enter the building,
258
00:52:50,667 --> 00:52:51,534
taking the other power feed with it,
for example, during a fire situation
259
00:53:16,726 --> 00:53:18,627
Verify that delivery of fuel and
equipment does not have limitations
260
00:53:18,662 --> 00:53:19,495
Verify thatdelryeryof fuel and
equipment does not have limitations,
261
00:53:19,829 --> 00:53:20,563
Verify that delivery of fuel and
equipment does not have limitations,
262
00:53:46,523 --> 00:53:52,928
Redundancy is great, but it comes with a |hefty pricetag that needs to be justified
263
00:53:52,929 --> 00:53:56,365
So again, when reviewing al criteria,
264
00:53:57,701 --> 00:54:00,903
work with that question, "what is the cost for downtine?"
265
00:54:38,041 --> 00:54:43,078
the loading bay of the building is also (serving the purpose of a holding area
266
00:54:43,346 --> 00:54:48,651
The holding area should be spacious enough Io handle potentially large equipment
267
00:54:48,918 --> 00:54:51,320
Equipment boxes may have
been in trucks on the roadside
268
00:54:51,821 --> 00:54:52,921
Equipment boxes may have
been in trucks on the roadside,
269
00:54:55,825 --> 00:55:01,664
and therefore are exposed to conditions
where it mav have attracted a lot of dust
270
00:55:01,898 --> 00:55:06,502
Therefore, never put boxes computer room, or even worse,
271
00:55:06,503 --> 00:55:11,807
unpack inside the computer room, las this will bring the dust inside,
272
00:55:11,808 --> 00:55:16,278
which could cause unavailability
or worse, even start a fire.
273
00:55:16,913 --> 00:55:20,849
Arrange for a proper unpacking
and garbage disposal area
274
00:55:21,117 --> 00:55:26,955
Ideally, during opening hours the
holding area has secunty guards present
275
00:55:29,893 --> 00:55:35,197
you should at least arrange for CCTV cameras that overtook this area
276
00:56:04,194 --> 00:56:09,264
It is a good practice to not power on
the equipment right away, as mentioned.
277
00:56:12,469 --> 00:56:15,904
environmental conditions the
equipment has been exposed to
278
00:56:23,079 --> 00:56:27,316
Sometimes you power up the
equipment for the first time and it fails.
279
00:56:31,054 --> 00:56:35,324
Never power on equipment for the first time in the computer room itself,
280
00:56:35,325 --> 00:56:38,527
since sometimes a faulty power supply
281
00:56:38,528 --> 00:56:43,031
could literally bring the entire rack or parts of the computer room down
282
00:56:43,032 --> 00:56:46,802
The equipment may even burn out.
In the rare cases,
283
00:56:47,036 --> 00:56:52,341
Keep systems in the staging area until it is ready for production
284
00:56:54,210 --> 00:56:59,281
it is recommended to have a fire protection system in place as well
285
00:56:59,549 --> 00:57:05,621
For some devices, such as storage equipment or new generation mainframes,
286
00:57:09,893 --> 00:57:16,565
In fact, it is not uncommon for this
equipment to be pre-staged by your vendor,
287
00:57:16,566 --> 00:57:22,171
| and once on site, the equipment is directly installed in the computer room
288
00:57:28,812 --> 00:57:31,713
you should connect to a separate PDU,
289
00:57:35,718 --> 00:57:39,121
In other words, avoid using the UPS
290
00:57:43,126 --> 00:57:47,129
Where it is not possible
o have a separate staging area,
291
00:57:47,130 --> 00:57:49,531
you may consider using a meeting room,
292
00:57:49,532 --> 00:57:52,968
but do realize that when the building doses in the evening,
293
00:58:01,211 --> 00:58:05,981
During staging, the equipment is tested
from a facility point of view.
294
00:58:05,982 --> 00:58:11,587
and once completed, the IT department can take over installing their parts.
295
00:58:15,525 --> 00:58:20,062
depending on the system’s functions,
of course, and further testing with users
296
00:58:20,063 --> 00:58:24,066
until the point where the system is ready
to be installed in the computer room,
297
00:58:24,334 --> 00:58:27,536
getting the system into production
298
00:58:30,440 --> 00:58:34,142
equipped with power conditioning
and power backup protection
299
00:58:37,881 --> 00:58:40,549
and have low electromagnetic fields
300
00:58:40,817 --> 00:58:45,888
so that systems can operate with a minimum risk of interruption
301
00:58:45,889 --> 00:58:50,893
Since this room is housing all
mission-critical equipment of a business.
302
00:58:50,894 --> 00:58:54,897
you need to ensure that appropriate security measures are implemented,
303
00:59:03,907 --> 00:59:10,078
so that quick action to detect and suppress a possible fire can be executed,
304
00:59:16,719 --> 00:59:20,122
Computer rooms should have low EMF levels.
305
00:59:20,123 --> 00:59:23,625
this since high levels could cause issues
306
00:59:23,626 --> 00:59:29,231
Avoid placing transformers
or UPS systems in the computer room
307
00:59:32,702 --> 00:59:36,371
you need to ensure that
there is an appropriate distance
308
00:59:40,376 --> 00:59:44,880
Also, make sure that movement into the computer room is limited
309
00:59:44,881 --> 00:59:47,516
People should only enter the computer room
310
00:59:50,720 --> 00:59:54,990
such as installing a new server or perhaps changing a patch code
311
00:59:55,258 --> 00:59:56,325
People should not have a need to enter the computer room,
312
01:00:03,232 --> 01:00:05,634
can all be done remotely nowadays
313
01:00:09,606 --> 01:00:13,342
to avoid disturbances
to the computer room environment
314
01:00:13,343 --> 01:00:19,181
The media storage area serves as the room where master copies of software,
315
01:00:23,686 --> 01:00:28,490
This area should be secure
and separate from any other area
316
01:00:28,491 --> 01:00:33,295
Realize that backup data may
be required for restore purposes
317
01:00:33,296 --> 01:00:38,066
and also, CCTV recordings should be
stored in a separate building
318
01:00:43,272 --> 01:00:43,739
most commonly a fire, all this
data gets potentially destroyed.
319
01:00:47,310 --> 01:00:51,580
Ideally, the media storage room
is further away from the computer room
320
01:01:06,996 --> 01:01:10,732
The media storage room should be
environmentally controlled and monitored,
321
01:01:10,733 --> 01:01:17,873
so that at any temperature and/or humidity
violation will be immediately detected
322
01:01:18,174 --> 01:01:24,312
Ideally, the media storage area is in a different building/on a different floor
323
01:01:24,580 --> 01:01:29,618
Backup tapes of production data
should always be stored off-site,
324
01:01:36,526 --> 01:01:41,329
Service companies offer the service
to store your media in special vaults
325
01:01:41,330 --> 01:01:44,232
to protect against the heat and humidity
326
01:01:44,500 --> 01:01:47,703
Do realize that during transport, however,
327
01:01:47,704 --> 01:01:51,406
backup media gets exposed to potentially
328
01:01:59,415 --> 01:02:01,516
looking at temperature and humidity
329
01:02:01,517 --> 01:02:02,851
and this could affect the lifespan
of your magnetic media
330
01:02:04,387 --> 01:02:05,487
and this could affect the lift
ir magnetic media
331
01:02:05,755 --> 01:02:10,292
You may consider making use of
mini temperature and humidity sensors,
332
01:02:13,229 --> 01:02:18,266
which then monitors the environmental
conditions over a period of time
333
01:02:18,267 --> 01:02:23,038
This will then allow you to review and detect if there are any
334
01:02:23,039 --> 01:02:27,843
reasons for concern caused during the transport of your media
335
01:02:27,844 --> 01:02:32,881
Finally, secure your data
with passwords and/or encryption
336
01:03:00,943 --> 01:03:01,376
UPS systems should be in a separate room.
337
01:03:01,377 --> 01:03:04,079
UPS systems should be in a separate room
338
01:03:04,080 --> 01:03:08,049
Some vendors place the UPS equipment in a nineteen inch rack type of configuration,
339
01:03:08,050 --> 01:03:10,218
Some vendors place the UPS equipment in a
nineteen inch rack type of configuration
340
01:03:15,525 --> 01:03:22,197
you should not put UPS systems side by side with your computer and network equipment
341
01:03:22,465 --> 01:03:28,336
UPS systems emit electromagnetic fields
which may affect your ICT equipment
342
01:03:32,108 --> 01:03:34,609
try to have at least two or
three rack space units unoccupied
343
01:03:34,744 --> 01:03:35,310
to have at least two
LU
ree rack
e units unoccu
344
01:03:35,344 --> 01:03:36,378
to have at least two
UI
iree rack
units unoccu
345
01:03:49,392 --> 01:03:54,429
so it is important to have cooling
equipment installed in the UPS room
346
01:04:08,277 --> 01:04:13,348
Most data centers combine
the batteries with the UPS systems
347
01:04:18,354 --> 01:04:23,658
but at the cost of some additional level
of risk if the batteries catch on fire,
348
01:04:23,659 --> 01:04:27,929
it may also affect the UPS systems they are supporting
349
01:04:38,040 --> 01:04:41,509
This battery is known as the flooded cell,
350
01:04:41,510 --> 01:04:42,077
and it is also known as the wet cell or vented cell battery.
351
01:04:42,211 --> 01:04:46,815
UI
■ and it is also known asg ie wet cel or vented cell batt
352
01:05:08,371 --> 01:05:08,970
would be a good practice
to detect any potential risk occurring
353
01:05:10,306 --> 01:05:12,073
would be a
Io detect any potential risk occurring
354
01:05:16,846 --> 01:05:19,514
to make sure that batteries are operating
355
01:05:27,189 --> 01:05:29,591
This is especially the case
when using SLA or VRLA batteries
356
01:05:51,914 --> 01:05:57,485
you can ensure that maintenance and
other activities on facility's equipment
357
01:05:57,486 --> 01:06:02,791
does not require individuals to go
into the mission-critical computer room.
358
01:06:11,600 --> 01:06:17,706
between facilities and ICT equipment. and related maintenance activities
359
01:06:22,745 --> 01:06:25,647
due to the amount of floor space required
360
01:06:25,915 --> 01:06:32,320
and therefore, not every data center owner
is in favor of this kind of solution
361
01:06:32,588 --> 01:06:37,659
Here you can see a typical
data center set-up looking from the top
362
01:06:42,164 --> 01:06:47,736
In another setup, air conditioners
are located outside the computer room
363
01:06:48,004 --> 01:06:52,507
and have been placed
in a service corridor around the room
364
01:06:52,508 --> 01:06:57,812
Air conditioners are still able to blow cold air under the raised floor structure,
365
01:07:19,068 --> 01:07:22,003
but instead of using a service corridor,
366
01:07:45,394 --> 01:07:53,101
The genset can be virtually in any location within or outside the building
367
01:08:02,411 --> 01:08:09,818
vibration, noise and exhaust fumes, which are created when the generator is running
368
01:08:20,463 --> 01:08:27,135
Fuel tanks need to be sized and placed in accordance with local regulations
369
01:08:32,174 --> 01:08:32,607
whereas in other countries they may be required to be above ground,
370
01:08:33,075 --> 01:08:34,109
whereas in other countries they may be required to be above ground,
371
01:08:36,479 --> 01:08:37,278
whereas in other countries the/* may be required to be above ground,
372
01:08:43,119 --> 01:08:46,020
The location of the fuel tank relatively
373
01:08:56,398 --> 01:09:02,504
Re-fuel points should be at the location [such that they are in a secure location,
374
01:09:30,800 --> 01:09:36,371
The Meet-Me or entrance room, or sometimes called handover room or carrier room,
375
01:09:51,320 --> 01:09:51,953
Be aware that in a shared building,
376
01:09:52,021 --> 01:09:53,688
Be aware that in a shared building
377
01:09:53,689 --> 01:09:57,926
this room may be under management control of the building owner
378
01:10:12,041 --> 01:10:18,146
It is not uncommon in a shared building to find these rooms in a somewhat poor state
379
01:10:23,953 --> 01:10:29,557
the telecommunication provider may allow for the outdoor network connection
380
01:10:32,461 --> 01:10:37,765
so that is now under full management
control of the data center itself
381
01:10:55,584 --> 01:10:58,486
and sometimes rectifiers and batteries,
382
01:11:01,156 --> 01:11:07,795
it should be equipped with smoke detection sensors and the fire suppression system
383
01:11:17,373 --> 01:11:23,745
Having security personnel at an open counter or desk is not always appropriate
384
01:11:39,128 --> 01:11:42,096
There are a variety of ratings,
385
01:11:53,242 --> 01:11:59,113
make sure that there is adequate er quality and backup power installed
386
01:12:23,372 --> 01:12:29,444
Similar as to other rooms, this room is ideally separate and secure,
387
01:12:29,445 --> 01:12:34,482
although it is not uncommon that this room is combined with the NOC,
388
01:12:40,889 --> 01:12:46,494
the room should have appropriate levels of protection, control of power quality,
389
01:12:46,495 --> 01:12:49,163
have environmental controls in place
390
01:12:49,164 --> 01:12:55,002
which are monitored and supported by fire protection and other safety measures,
391
01:13:03,212 --> 01:13:06,714
Staff who monitors the environment
392
01:13:12,020 --> 01:13:17,058
it is a matter of health
and human safety, as well as security
393
01:13:20,529 --> 01:13:21,095
which could create contamination in the computer room
394
01:13:22,698 --> 01:13:23,965
which could create contamination
in the computer room
395
01:13:29,304 --> 01:13:34,876
you wish to avoid human movement in the data center as much as possible,
396
01:13:34,877 --> 01:13:35,610
this applies to the computer room
and all supporting areas
397
01:13:37,646 --> 01:13:39,113
this applies to the computer room
id all sui
areas
398
01:13:40,983 --> 01:13:45,520
some work needs to be done inside
the computer room and supporting rooms
399
01:13:53,462 --> 01:13:59,033
you need to ensure that the monitoring
systems are connected to the UPS,
400
01:14:07,075 --> 01:14:13,714
you now should have a good idea which rooms are required or desired,
401
01:14:22,257 --> 01:14:27,528
security, environmental controls,
for monitoring temperature and humidity,
402
01:14:34,670 --> 01:14:40,308
you require sufficient space for each supporting room, and where possible,
403
01:14:40,309 --> 01:14:46,948
physcial separation of redundant
equipment may be desired or even required
404
01:14:55,157 --> 01:15:00,194
so keep that in mind if the design will be based on Rated 4
405
01:15:00,462 --> 01:15:06,834
On this slide, we can see some of the most
common design mistakes occurring
406
01:15:07,102 --> 01:15:12,440
Some designers place main switchboards
inside the computer room
407
01:15:17,479 --> 01:15:22,783
the more EMF is created
which could impact your ICT equipment
408
01:15:23,051 --> 01:15:29,690
Furthermore, the higher the power rating, the more risk of fire and the explosion
409
01:15:29,691 --> 01:15:34,228
High power switchboards should be outside of the computer room.
410
01:15:37,933 --> 01:15:41,936
It is, of course, acceptable to have the electrical switchboards,
411
01:15:45,440 --> 01:15:51,546
inside the computer room, since they
are often a relatively low power ratinq
412
01:16:02,991 --> 01:16:06,427
such as electrical and mechanical systems,
413
01:16:06,428 --> 01:16:11,465
as much as possible outside the computer
room and place them in a separate room,
414
01:16:15,971 --> 01:16:23,411
Another design flaw is when access to an equipment room goes through another room
415
01:16:23,412 --> 01:16:29,550
For example, you have to go through the computer room to reach the UPS room
416
01:16:32,754 --> 01:16:36,424
Access through other rooms is only allowed
417
01:16:40,729 --> 01:16:46,267
For example, it is acceptable to have access to the battery room
418
01:16:56,945 --> 01:17:02,249
It could be arqued that an enterprise
data center is a more stable environment.
419
01:17:02,250 --> 01:17:05,152
and not many changes are happening
420
01:17:05,153 --> 01:17:08,389
However in a commercial data center,
421
01:17:08,390 --> 01:17:13,461
where many changes may take place
and a lot of movement is going on,
422
01:17:13,662 --> 01:17:16,597
this would be very much unacceptable
423
01:17:21,136 --> 01:17:25,906
Although anyone understands
the benefit of having a service corridor,
424
01:17:33,649 --> 01:17:35,416
In this module, you have learned
that the proper site selection is critical
425
01:17:35,417 --> 01:17:39,987
In this module, you have teamed that the proper site selection is critical
426
01:17:39,988 --> 01:17:43,724
to the long-term success of a data center
427
01:17:43,725 --> 01:17:44,358
Site selection is often challenging
428
01:17:44,626 --> 01:17:45,993
Site selection is often challenging,
429
01:17:51,466 --> 01:17:56,771
and the technical departments
is well as the limitation of the budgets
430
01:18:44,453 --> 01:18:45,252
tor need to be installed. Location wise, where do you in:
431
01:18:46,621 --> 01:18:48,989
n. what is the keyword to consider?
432
01:19:26,595 --> 01:19:30,097
There are mainly two different types of raised floor tiles
433
01:19:30,098 --> 01:19:35,169
one is the die formed welded steel tile, which is hollow on the inside.
434
01:19:39,674 --> 01:19:44,178
which is used to bring the cold air from under the raised floor into the room
435
01:19:45,147 --> 01:19:45,813
The other type is the die formed welded steel shell tile,
436
01:19:52,420 --> 01:19:56,690
This is a tile where there is
cement or concrete construction
437
01:20:00,162 --> 01:20:05,466
Other tiles exist, such as
galvanized tiles, which can be harmful,
438
01:20:05,467 --> 01:20:09,470
because they can be contaminated with zinc whiskers
439
01:20:17,712 --> 01:20:19,013
and therefore, possibly end up on electrical circuits in the systems
440
01:20:36,064 --> 01:20:41,635
Some data centers prefer carbon
fiber floor tiles, which are very strong
441
01:21:03,358 --> 01:21:04,491
are covered with a vinyl finishing
442
01:21:04,759 --> 01:21:08,495
and this is often referred to as HPL,
443
01:21:17,005 --> 01:21:20,708
which make up a raised floor structure
444
01:21:27,649 --> 01:21:30,784
or drilling them to the concrete slab
445
01:21:30,785 --> 01:21:33,988
Sometime it is done in an alternating way,
446
01:21:37,459 --> 01:21:40,928
whereas the next four pedestals are glued,
447
01:21:44,666 --> 01:21:46,233
This will then save on installation time and also cost,
448
01:21:48,937 --> 01:21:53,707
and will ensure that the concrete floor not having many drill holes,
449
01:21:53,708 --> 01:21:57,678
which potentially could weaken the floor
450
01:22:01,950 --> 01:22:08,822
The first one to discuss is uniform distributed load, shortly known as UDL
451
01:22:15,764 --> 01:22:20,801
since now the load is spread evenly
over the enure surface area
452
01:22:21,102 --> 01:22:27,174
Ratings are expressed in kilo newton per square meter or as pounds per square feet
453
01:22:32,480 --> 01:22:37,818
so a conversion needs to be done
from kilograms to kilonewton
454
01:22:48,997 --> 01:22:55,369
using the conversion that one kilonewton
is equal to one hundred kilograms
455
01:22:55,637 --> 01:23:00,174
Uniform distributed load, by the way, is hardly found in data centers,
456
01:23:00,175 --> 01:23:02,543
this because of most equipment is standing on casters or feet.
457
01:23:03,712 --> 01:23:05,479
this because of most equipment is standing on casters or feet
458
01:23:05,747 --> 01:23:10,784
Concentrated load, which is also called point load, is a single point,
459
01:23:10,785 --> 01:23:16,623
whereby a potential high load is placed on a very small area of the tile
460
01:23:16,624 --> 01:23:22,763
In the standard, it is deined as the size of the point being 25 mm in a square,
461
01:23:26,468 --> 01:23:31,271
As you can imagine, a point load is much more difficult to handle
462
01:23:31,272 --> 01:23:34,441
compared to uniform distributed load
463
01:23:39,214 --> 01:23:44,785
and in most cases also the stringers, it is the strongest part of the tile
464
01:23:44,786 --> 01:23:49,556
Stringers are the steel or aluminum
channels or square tubes,
465
01:23:49,557 --> 01:23:55,162
which are fastened between pedestal heads
in order to provide lateral stability
466
01:23:55,163 --> 01:23:59,666
With that said, the weakest point of the tile is the dead center,
467
01:24:05,006 --> 01:24:07,908
Standards do allow for the raised floor tile to bend a bit,
468
01:24:19,354 --> 01:24:25,459
which means that the tile won't bend back
anymore when the point load is removed
469
01:24:25,727 --> 01:24:32,366
The bottom line is, you need to make sure
that you do not overload the floor tile
470
01:24:37,138 --> 01:24:41,909
First, you can place small square metal plates under the caster
471
01:24:44,279 --> 01:24:48,582
so that the surface area gets bigger, and therefore spreading the load
472
01:24:48,850 --> 01:24:54,688
Another option is to place an additional ■pedestal under the raised floor tile,
473
01:24:59,227 --> 01:24:59,660
Rolling load occurs when a caster or wheel, as it is called,
474
01:25:01,496 --> 01:25:02,062
Rolling load occurs when
a caster or wheel, as it is called
475
01:25:03,131 --> 01:25:03,931
5
| Rolling load occurs when| caster or wheel, as it is called,
476
01:25:10,338 --> 01:25:10,871
because it can cause damage to the top layer of the floor tiles
477
01:25:11,406 --> 01:25:13,307
becausejt^ancause damage to the too layer of the floor tiles
478
01:25:13,842 --> 01:25:17,277
It also stretches the tile tremendously,
479
01:25:20,482 --> 01:25:25,018
it more or less creates a wave effect
from a bending point of view,
480
01:25:29,491 --> 01:25:35,062
To protect the floor, you can cover the floor in order to prevent damage
481
01:25:40,135 --> 01:25:43,303
since cardboard is often very dusty,
482
01:25:43,304 --> 01:25:47,808
and therefore, creates contamination inside the computer room.
483
01:25:52,881 --> 01:25:54,982
to protect the floor from bending
484
01:25:55,517 --> 01:26:02,456
It is therefore recommended to use metal [plates or metal sheets, such as aluminium
485
01:26:02,457 --> 01:26:06,760
For example, you can take aplate of 1x2 meters or 3x6 feet,
486
01:26:07,061 --> 01:26:07,995
| For example, you can take,
plateof 1x2 meters or 3x6 feet
487
01:26:17,872 --> 01:26:21,608
and roll the load over the first plate to the second plate
488
01:26:21,876 --> 01:26:26,914
Once the load is on the second plate
you can lift up the first plate
489
01:26:30,118 --> 01:26:33,287
Of course, if this is tedious to do,
490
01:26:33,288 --> 01:26:38,358
and a long distance need to be crossed with many equipment racks to be moved,
491
01:26:38,359 --> 01:26:44,998
you can purchase more than two plates, covering your entire floor in one go
492
01:26:50,305 --> 01:26:56,176
that may create nasty cuts when in contact with arms and legs
493
01:27:13,728 --> 01:27:18,232
There are various international
standards for raised floors.
494
01:27:18,233 --> 01:27:24,304
The UK-PSA MOB is the standard that is most widely used.
495
01:27:24,305 --> 01:27:28,041
The property services agency or PSA
496
01:27:28,042 --> 01:27:32,546
is an organization in the UK that provides standards for buildings
497
01:27:32,547 --> 01:27:37,618
The organization no longer exists, but the standard continues to live on
498
01:27:43,725 --> 01:27:46,893
ranging from light to extra heavy
499
01:27:47,161 --> 01:27:52,532
The definition of heavy and extra heavy looks the same for load factors
500
01:27:55,203 --> 01:28:01,041
must also be able to sustain a load
of eleven kilonewtons over four points.
501
01:28:01,309 --> 01:28:06,913
and each of these points are defined as a twenty five millimeter square area
502
01:28:20,695 --> 01:28:25,732
ths can be compared to a mid-size car ^standing on a raised floor board,
503
01:28:35,576 --> 01:28:40,647
but the values are now displayed
using the imperial system
504
01:28:54,195 --> 01:29:00,300
For reference purposes, the names of these standards are displayed on this slide
505
01:29:08,810 --> 01:29:15,749
but also raised floor structure itself,
since every tile has a certain weight
506
01:29:15,750 --> 01:29:21,021
On this slide, you see examples of the weight per tile
507
01:29:21,656 --> 01:29:24,558
the weight identified for
each tile is approximate
508
01:29:25,059 --> 01:29:29,830
since it differs per manufacturer, so if you need the exact weight,
509
01:29:34,335 --> 01:29:40,707
In some rare cases, it may happen that the supplier is trying to cut comers
510
01:29:45,513 --> 01:29:51,885
It is especially the case when a customer is pushing for too much discount,
511
01:29:57,992 --> 01:30:01,728
This is. however, easy to discover
512
01:30:01,963 --> 01:30:07,300
During the build, you can go on srte, check on the various boxes
513
01:30:07,301 --> 01:30:12,072
and compare the part numbers with the part numbers of the data sheets,
514
01:30:20,114 --> 01:30:22,482
put the floor tile on the weight scale,
515
01:30:22,750 --> 01:30:27,821
and compare the weight with what
the original manufacturer has indicated
516
01:30:32,293 --> 01:30:36,329
Again, this happens in rare cases only,
517
01:30:36,330 --> 01:30:41,868
but now you know how you can verify that the floor tiles that you have ordered
518
01:30:41,869 --> 01:30:47,174
are the ones that are also delivered
land installed in your data center
519
01:30:47,175 --> 01:30:53,046
The values on this slide
in both metric and imperial numbers
520
01:30:55,683 --> 01:31:01,021
the raised floor is often used to
provide cooling to the ICT equipment.
521
01:31:01,022 --> 01:31:05,258
and to organize power and network cabling under the floor
522
01:31:05,526 --> 01:31:08,195
By placing cabling out of view,
523
01:31:11,933 --> 01:31:17,003
although most data centers place the network cables in the ceiling area,
524
01:31:17,004 --> 01:31:19,639
and this if for a very good reason
525
01:31:19,907 --> 01:31:26,546
For traditional data centers, deploying
racks of approximately 3 kw per rack
526
01:31:26,547 --> 01:31:32,118
it is required to have a raised floor height of at least forty centimeters,
527
01:31:36,424 --> 01:31:40,660
This height is measured from the concrete slab of the building
528
01:31:40,661 --> 01:31:43,864
to the bottom of the raised floor tile
529
01:32:11,259 --> 01:32:14,160
which is equivalent to twenty four inches
530
01:32:14,428 --> 01:32:18,698
Be aware that increasing the cooling
capacity in the computer room
531
01:32:18,699 --> 01:32:23,503
is not as simple as just increasing the height of the raised floor
532
01:32:27,441 --> 01:32:30,677
as well as an air volume displacement,
533
01:32:30,678 --> 01:32:35,715
which is indicated as cubic feet per minute or cubic meter per hour,
534
01:32:35,716 --> 01:32:41,054
all play an important rote and you must ensure that they are all in proper balance,
535
01:32:44,759 --> 01:32:50,864
When installing power and/or network cabling pathways under the raised floor,
536
01:32:50,865 --> 01:32:54,834
it's important not to impact the air flow
537
01:32:55,136 --> 01:33:00,440
Carefully review the drawings
of the proposed cable tray routing
538
01:33:00,441 --> 01:33:03,643
This, since the issues are created
539
01:33:03,644 --> 01:33:07,914
when cable trays are placed in front of air conditioner outlets,
540
01:33:13,254 --> 01:33:13,753
It is better to use wide
and low cable trays,
541
01:33:17,425 --> 01:33:20,627
instead of narrow and high cable trays,
542
01:33:37,411 --> 01:33:43,550
so cabling from under the raised floor
can be guided into the back of the rack
543
01:33:43,818 --> 01:33:48,355
Be aware that when you cut the metal shell of the raised floor,
544
01:33:50,024 --> 01:33:50,523
it will have very sharp edge
545
01:33:54,996 --> 01:34:00,066
It is not hard to imagine that if the raised floor tile cuts a power cable,
546
01:34:00,067 --> 01:34:05,639
this could cause a dangerous situation, as well as data center unavailability
547
01:34:05,640 --> 01:34:11,478
It is therefore recommended to install a protection coyeron the cut out,
548
01:34:11,479 --> 01:34:15,215
to prevent any cable damage from occuring
549
01:34:15,750 --> 01:34:21,588
Ideally, you specify the plastic covers
in the agreement with the vendor,
550
01:34:21,589 --> 01:34:25,325
in order to avoid extra charges later on
551
01:34:35,970 --> 01:34:40,206
The more openings you have in the floor, the more pressure you lose.
552
01:34:42,510 --> 01:34:44,177
and that leads to less cooling
capacity being available
553
01:34:44,478 --> 01:34:49,516
Openings under the rack are typically located at the back of each rack
554
01:34:49,784 --> 01:34:56,389
If this opening is not sealed, cold air will be pushed into the back of the rack,
555
01:34:56,390 --> 01:35:00,126
where it serves no purpose whatsoever
556
01:35:00,394 --> 01:35:05,432
The objective of cold air is to deliver at the intake equipment,
557
01:35:05,433 --> 01:35:05,865
where the cold air will literally be sucked into the equipment,
558
01:35:09,737 --> 01:35:12,372
to provide the required cooling
559
01:35:12,640 --> 01:35:19,579
There are few options to choose for
closing the openings under the rack
560
01:35:19,847 --> 01:35:25,151
You can purchase fire rated pillows, which look like small bean bags
561
01:35:25,152 --> 01:35:30,190
You can put them on top of the opening, allowing the cabling to pass through.
562
01:35:30,458 --> 01:35:33,126
It is a fairly inexpensive solution,
563
01:35:40,034 --> 01:35:44,804
Another and more professional option is to use grommets.
564
01:35:44,805 --> 01:35:45,705
The principle of a
grommet is that two brushes
565
01:35:56,217 --> 01:36:01,254
Grommets are a very good solution
but they are more costly.
566
01:36:01,255 --> 01:36:04,190
Overall, it is the better solution
compared to the pillows,
567
01:36:04,558 --> 01:36:05,325
OyeraM, it is the better solution
568
01:36:05,559 --> 01:36:07,694
and you only need to buy it once
569
01:36:12,466 --> 01:36:18,838
Some organizations go to the low
budget route, using fire rated rubber.
570
01:36:20,040 --> 01:36:20,940
which can be effective as well
571
01:36:20,941 --> 01:36:25,979
but it will not provide a nice finish from an aesthetic point of view
572
01:36:26,514 --> 01:36:30,517
When air conditioning units are
placed inside the computer room,
573
01:36:30,518 --> 01:36:33,720
you need to make sure that
the vibration from the air conditioner
574
01:36:33,721 --> 01:36:34,154
is not transferred into the raised floor
575
01:36:36,190 --> 01:36:36,890
is not transferred into the raised floor
576
01:36:37,158 --> 01:36:42,262
Vibration in the raised floor will transfer to vibration in ICT equipment,
577
01:36:46,267 --> 01:36:51,304
Therefore, leave a gap between the raised floor and the air conditioning frame,
578
01:36:51,305 --> 01:36:56,643
to ensure that vibration doesn't transfer to the raised floor.
579
01:37:06,987 --> 01:37:13,393
Lastly, avoid that the area under the floor
ends up being a garbage bin
580
01:37:13,394 --> 01:37:18,131
The area under the raised floor
needs to remain as clean as possible,
581
01:37:21,836 --> 01:37:27,974
Dust too is unwanted, since the air flow
will lake the dust into the room,
582
01:37:31,946 --> 01:37:36,216
When the raised floor construction
is finalized during the build phase,
583
01:37:39,153 --> 01:37:41,654
since contractors have the tendency
to throw their waste under the floor,
584
01:37:43,324 --> 01:37:43,957
since contractors have the tendency to throw their waste under the floor
585
01:37:43,958 --> 01:37:47,260
believing that no one will be looking for it once the works are done
586
01:37:47,261 --> 01:37:48,461
believing that no one will be ng for it once the works are done
587
01:37:48,729 --> 01:37:54,567
If any debris is identified, then you request the contractor to take care of it,
588
01:37:54,568 --> 01:37:59,105
cleaning up the mess that they themselves have created
589
01:40:14,375 --> 01:40:15,908
Electric code indicates that every metal
part needs to be connected to the ground
590
01:40:15,909 --> 01:40:19,479
Electric code indicates that every metal part needs to be connected to the ground
591
01:40:19,747 --> 01:40:23,449
This also applies to the raised
floor structure of the computer room
592
01:40:45,773 --> 01:40:51,110
that is protecting the computer room
from high frequency noise currents,
593
01:41:00,587 --> 01:41:01,154
Note that with the increasing frequencies
of copper-based network cabling,
594
01:41:07,628 --> 01:41:13,733
it is anticipated that the high frequency shielding properties of an SRG
595
01:41:13,734 --> 01:41:17,703
will lose some of its purpose the future
596
01:41:23,010 --> 01:41:27,814
can be found in thelEEEl 100 standard
597
01:41:31,485 --> 01:41:36,589
at the perimeter of the room you need
to connect every pedestal to each other,
598
01:41:36,590 --> 01:41:39,258
after which you connect it to the ground.
599
01:41:39,493 --> 01:41:45,598
IEEE 1100 also indicates that you should create grounding mesh by. at the minimum,
600
01:41:50,971 --> 01:41:56,242
so that there is a dear 3x3 pedestal meshed grounding system
601
01:41:56,510 --> 01:42:02,882
All racks in the computer room need to be
ponded to the signal reference grid
602
01:42:19,099 --> 01:42:22,568
Serial bonding, therefore, is not allowed
603
01:42:22,569 --> 01:42:27,039
Serial bonding is the principle
of connecting one rack to the SRG,
604
01:42:27,407 --> 01:42:28,174
| Serial bonding is the prindptey of connecting onerack to the SRG,
605
01:42:35,616 --> 01:42:40,119
that if there is an interruption!
in the bonding from one to another rack,
606
01:42:56,069 --> 01:42:58,704
Lets have a look at the proper rack grounding by providing a visual example
607
01:42:58,705 --> 01:43:02,975
| Lets have a look at the proper rack rounding by providing a visual example
608
01:43:07,247 --> 01:43:13,986
and under the racks you see the raised
floor, pedestals and the concrete slab
609
01:43:18,425 --> 01:43:23,763
and route the ground wire under the rack,
where you connect it to the pedestal
610
01:43:26,366 --> 01:43:32,538
this has to be done for every
individual rack inside the computer room
611
01:43:35,976 --> 01:43:39,946
ideally, do not use a standard copper wire
612
01:43:43,717 --> 01:43:48,187
This, since high frequency noise currents
613
01:43:52,459 --> 01:43:55,394
similar to what normal electricity does
614
01:43:55,696 --> 01:43:58,331
High frequency noise currents tend
to go through the skin of the cable
615
01:44:00,734 --> 01:44:06,806
Therefore, you need to have a cable
with as much skin as possible,
616
01:44:06,807 --> 01:44:10,543
to create a low resistance path to ground
617
01:44:12,246 --> 01:44:14,146
For that reason it is required to use
a braided cable or flat copper strips,
618
01:44:32,399 --> 01:44:38,771
are well connected and corrosion-free,
to ensure good conductivity
619
01:45:41,101 --> 01:45:41,534
through the opening in the raised
floor tile into the back of the rack
620
01:45:53,447 --> 01:45:58,484
is to draw a cross on the tile, and the
cut out should be done in such a way
621
01:45:58,485 --> 01:46:01,954
that it does not touch any of these lines
622
01:46:02,189 --> 01:46:06,459
When using standard nineteen inch racks
you do not have to be worried.
623
01:46:09,896 --> 01:46:14,734
but at the edges where it is supported
by the pedestals and the stringers
624
01:46:16,036 --> 01:46:21,340
if you have properly aligned the uquipment racks to the raised floor tiles
625
01:46:26,146 --> 01:46:31,484
since this is the area that is to rest
on the head of the pedestal
626
01:46:31,485 --> 01:46:36,489
Ramps are often required, since the raised floor is of course,
627
01:46:40,727 --> 01:46:43,929
General guidance in the building codes
628
01:46:48,468 --> 01:46:53,472
This means in practice that for every [twelve units that you go horizontal,
629
01:47:18,999 --> 01:47:24,336
the longer the ramp wil be, and this may
take up a lot of space in the building
630
01:47:26,706 --> 01:47:27,173
Since it is a guideline, there is me leeway in the ratio to be used
631
01:47:29,309 --> 01:47:30,443
Since it is a guideline, there is some leeway in the ratio to be used
632
01:47:35,749 --> 01:47:41,353
or even a ratio of one to six
but do realize, the steeper the ramp,
633
01:47:44,791 --> 01:47:48,260
Furthermore, local regulations may exist,
634
01:47:51,731 --> 01:47:56,769
and therefore, verify this before you build a ramp that needs to be replaced
635
01:47:57,037 --> 01:47:59,104
because it does not get the necessary
approval from the local authorities
636
01:47:59,105 --> 01:48:03,142
becausejtdloesnot^get the necessary approval from the local authorities
637
01:48:03,143 --> 01:48:06,378
Also, consider the width of the ramp
638
01:48:17,224 --> 01:48:19,892
for the equipment to stand stationary
639
01:48:28,068 --> 01:48:29,869
you build a landing platform that is two meters or 6 5 feet in a square
640
01:48:32,172 --> 01:48:32,638
you build a landing platform that is two meters or 6.5 feet in a square
641
01:48:36,610 --> 01:48:42,181
you can, of course, use the floor in the
computer room as the landing platform
642
01:48:42,449 --> 01:48:47,786
In addition, since people will be moving equipment on and off the ramp,
643
01:48:47,787 --> 01:48:49,321
install a handrail for safety purposes
644
01:48:49,756 --> 01:48:50,990
install a handrail for safety purposes
645
01:48:59,733 --> 01:49:02,468
as part of the applicable regulations
646
01:49:02,469 --> 01:49:08,807
And even if it is not mandatory
lit is always advisable to install a handrail,
647
01:49:20,787 --> 01:49:25,024
so that you can identify the
steepness and the length of the ramp
648
01:49:25,292 --> 01:49:30,062
As mentioned, you may not have a long distance in the front of the door,
649
01:49:36,469 --> 01:49:42,274
The bottom example demonstrates a ramp that follows the one to six ratio
650
01:49:53,186 --> 01:49:59,592
By moving the ramp with the ratio of one to six directly on top of the ramp.
651
01:49:59,593 --> 01:50:06,198
following the ratio one to twelve, you can
easily identify the incline in steepness
652
01:50:11,004 --> 01:50:16,575
it will be twice as steep, as can be seen
on the right hand side of the image
653
01:50:29,122 --> 01:50:30,889
the area should cater for a dimension that is at least 2x2m or 6.5x6.5 feet
654
01:50:30,890 --> 01:50:38,397
the area should cater for a dimension khat is at least 2x2m or 6.5x6.5 feet
655
01:50:39,199 --> 01:50:42,901
In case the landing platform is built
alongside the computer room,
656
01:50:48,508 --> 01:50:52,244
or let the equipment stand stationary
657
01:50:52,479 --> 01:50:55,714
In this example, at the end of the ramp
658
01:50:55,715 --> 01:50:57,416
a landing platform is built that has la dimension of two by two meters
659
01:50:58,652 --> 01:51:01,553
a landing platform is built that has a dimension of two by two meters
660
01:51:06,059 --> 01:51:11,897
This so to accommodate easier turning
the equipment into the computer room,
661
01:51:11,898 --> 01:51:19,071
and also to allow the equipment to stand
stationary on the landing platform
662
01:51:42,562 --> 01:51:45,130
and also for the less abled people
663
01:51:45,398 --> 01:51:49,668
This may result in larger width in areas,
664
01:51:54,441 --> 01:51:57,576
Although some individuals might argue that those in the wheelchair
665
01:52:05,585 --> 01:52:10,656
and the computer room is often treated as any other space within the building
666
01:52:10,924 --> 01:52:14,359
And therefore, if such regulation exists.
667
01:52:37,817 --> 01:52:39,818
There are a few reasons for considering
implementing a suspended ceiling.
668
01:52:39,819 --> 01:52:42,054
There are a few reasons for considering
Kmotefnentina a suspended ceilino
669
01:52:45,925 --> 01:52:46,458
The first reason for implementing
is that it looks much nicer
670
01:52:47,293 --> 01:52:47,893
The first reason for imptementi K that it looks much nicer,
671
01:52:49,429 --> 01:52:50,295
The first reason for implementing
is that it looks much nicer,
672
01:52:50,563 --> 01:52:55,868
instead of looking at the concrete slab, pipes, cables and structural beams
673
01:52:56,436 --> 01:52:57,236
and this, of course, makes the data center look nicer
674
01:52:59,139 --> 01:52:59,838
and this, of course makes the data center look nicer
675
01:53:00,106 --> 01:53:02,775
The suspended ceiling is sometimes used
676
01:53:07,013 --> 01:53:09,348
By doing so, less gas is needed or the fire suppression system.
677
01:53:10,750 --> 01:53:11,283
By doing so, less gas is needed or the fire suppression system.
678
01:53:11,284 --> 01:53:16,321
and therefore, in most cases this can save a substantial amount of money
679
01:53:16,623 --> 01:53:19,758
Realize, however, that in order to do so.
680
01:53:19,759 --> 01:53:25,931
you need to verify the applicable fire safety code, if this is allowed or not
681
01:53:26,199 --> 01:53:30,435
A more prominent reason
or installing a suspended ceiling
682
01:53:51,758 --> 01:53:54,693
which get heated up by the same equipment.
683
01:53:54,694 --> 01:53:58,397
which will then blow the heat load out
from the back of the rack
684
01:54:11,177 --> 01:54:16,481
The vent of the air conditioner is sucking |the air from the suspended ceiling void,
685
01:54:30,096 --> 01:54:34,299
you need to make sure that the computer
room is appropriately dimensioned
686
01:54:34,300 --> 01:54:35,567
in terms of the raised floor height computer room height
687
01:54:37,770 --> 01:54:40,939
and the suspended ceiling void height
688
01:54:43,376 --> 01:54:48,680
the raised floor height needs to be at least forty centimeters or sixteen inches,
689
01:54:48,681 --> 01:54:50,182
with the preference of sixty
centimeters or twenty four inches
690
01:54:52,318 --> 01:54:53,485
with the preference of sixty centimeters or twenty four inches
691
01:54:54,020 --> 01:54:54,486
The computer room needs to be at least 260cm, or 8.6ft in height,
692
01:54:57,090 --> 01:54:59,291
The computer room needs to be at least 260cm, or 8.6ft in height,
693
01:54:59,859 --> 01:55:00,392
The computer room needs to be at least 260cm, or 8 6ft in height
694
01:55:00,393 --> 01:55:05,998
measured from the top of the raised floor [to the bottom of the suspended ceiling
695
01:55:14,507 --> 01:55:19,011
then additional height needs to be
catered for in your computer room
696
01:55:22,448 --> 01:55:26,718
in case you are using an overhead
network and/or power cable trays
697
01:55:33,927 --> 01:55:38,463
The standards require that sprinkler and gas nozzle head
698
01:55:42,435 --> 01:55:46,672
or roughly 1 3 ft of clearance underneath
699
01:55:46,673 --> 01:55:53,312
This is so to ensure that water or gas
can be appropriately dispersed.
700
01:56:14,067 --> 01:56:19,404
the area above the suspended ceiling should be at least sixty centimetres,
701
01:56:19,405 --> 01:56:22,841
but ideally, eighty centimeters in height
702
01:56:32,185 --> 01:56:38,256
Ideally, the building has a slab to slab height of 3.8 meters,
703
01:56:38,257 --> 01:56:45,197
which is roughly 12.5 feet, to cater for the example dimensions provided just now
704
01:56:45,465 --> 01:56:50,502
Before you rewind the video, because you feel you have missed it out, don't worry,
705
01:56:58,511 --> 01:56:59,144
you may need to look at alternative ways to set up the data center
706
01:56:59,312 --> 01:57:00,078
you may need to look at alternative ways to set up the data center.
707
01:57:00,613 --> 01:57:02,247
you may need to look at alternative ways to set up the data center
708
01:57:02,482 --> 01:57:04,883
There are a variety of options available,
709
01:57:05,518 --> 01:57:06,752
which I will discuss in
the cooling infrastructure module,
710
01:57:08,354 --> 01:57:11,523
referring to non - raised floor solutions
711
01:57:25,338 --> 01:57:32,511
which is not desirable, even if your air
conditioner has a filter system installed
712
01:57:32,779 --> 01:57:38,083
Similar as under the floor, contractors
may have used your ceiling as a garbage bin
713
01:57:42,355 --> 01:57:47,092
so that nothing slides off and ends up in your equipment rack
714
01:57:47,427 --> 01:57:53,765
Also, in the rare case of a gas-based
fire suppression system being activated,
715
01:57:53,766 --> 01:57:58,837
it will often create the effect off
suspended ceiling boards being displaced,
716
01:57:58,838 --> 01:57:59,438
due to the increased air pressure,
717
01:58:00,373 --> 01:58:00,972
due to the increased air pressure,
718
01:58:16,122 --> 01:58:18,290
Before looking at the computer room
719
01:58:22,261 --> 01:58:28,900
let's have a look at what actually happens when a suspended ceiling is not existing
720
01:58:33,306 --> 01:58:34,973
and by means of perforated tiles,
721
01:58:35,041 --> 01:58:39,578
the cold air will end up in the
computer room in front of the equipment
722
01:58:39,846 --> 01:58:41,413
The equipment sucks the cold air in, and blows out the heat load
723
01:58:42,548 --> 01:58:44,216
The equipment sucks the cold air in,
and blows out the heat load
724
01:58:48,588 --> 01:58:53,658
Without a suspended ceiling, the hot air will freely travel through the room,
725
01:58:59,232 --> 01:59:05,337
Mixing of cold air will have a negative
impact on the efficiency of cooling
726
01:59:05,605 --> 01:59:10,108
Now that we have seen the computer room without the suspended ceiling.
727
01:59:10,109 --> 01:59:15,180
lets have a look at the computer room ■with the suspended ceiling installed
728
01:59:28,728 --> 01:59:35,100
The hot air travels up. and since now
there are openings in the ceiling area,
729
01:59:38,838 --> 01:59:42,541
which optimizes the cooling efficiency
730
01:59:42,542 --> 01:59:46,011
As promised during the previous slide,
731
01:59:50,516 --> 01:59:55,820
The raised floor needs to be at least
forty centimetres or sixteen inches,
77873
Can't find what you're looking for?
Get subtitles in any language from opensubtitles.com, and translate them here.